Features

  • Accuracy Class: 0.5
  • Operating Frequency: 50Hz to 200KHz
  • Input Voltage: 230V 1phase / 400V 3phase
  • Input Current Range: 1-150A without loading
  • Power-Frequency withstand voltage: 2.5KV 60”
  • Insulation Resistance : ≥ 100Mohm with DC 500V
  • Voltage Level: 660/720V
  • Lifetime ≥ 10years
  • Flexible installation

Applications

  • Smart Metering
  • Mainly for isolating, collecting, and measuring AC Current signals in the primary main circuit
  • Analog to Digital Circuit
  • Sensing Overload Current
  • Ground fault detection

Dimensions and characteristics of OWCT16M-xxxT-xxx Split Core Current Transformer-Ferrite material

A(mm)B(mm)C(mm)Series spec
36.8±0.348.5±0.516.0±0.5
ItemUnitOWCT16M-
1KT-100A
OWCT16M-
2KT-100A
OWCT16M-
3KT-100A
OWCT16M-
4KT-100A
OWCT16M-
5KT-100A
Turns Ratio(Kr)1000:12000:13000:14000:15000:1
Rated Input CurrentA(ac)100100100100100
FrequencyHz50/6050/6050/6050/6050/60
Rated Output CurrentmA (ac)10050502520
Rated Accuracy Error±%0.50.50.50.50.5
Phase rated Error±Minutes60(RL=0)45(RL=0)45(RL=0)45(RL=0)45(RL=0)
Linearity±%0.30.30.30.30.3
Rated sampling resistanceΩ2010075300400
Rated sampling voltageV(ac)253.757.58
Measuring Input
Current range
A(ac)0-100
(RL≤20Ω)
0-150
(RL≤100Ω)
0-150
(RL≤75Ω)
0-150
(RL≤50Ω)
0-150
(RL≤50Ω)
Max. Input CurrentA(ac)120
(RL≤10Ω)
200
(RL≤10Ω)
190
(RL≤10Ω)
180
(RL≤10Ω)
160
(RL≤10Ω)
Inner ResistorΩ41±5125±15293±30565±50860±80
Power Freq. VoltageV2500V,60”2500V,60”2500V,60”2500V,60”2500V,60”
Insulation ResistanceMΩ Min.
500Vac
500500500500500